KVAFLA (Primary)125% OF FLA75°C ConductorMOCPFLA (Secondary)125% OF FLA75°C ConductorBonding
1518.0622.57122041.6852.10610
3036.1245.1584083.37104.2126
4554.1967.73460125.05156.322/06
7590.31112.892100208.42260.533004
112.5135.47169.342/0150312.63390.796003
150180.63225.794/0225416.85521.062 x 3002
225270.95338.69500300625.27781.5972 x 6001/0
300361.27451.592 x 4/0400833.701042.134 x 3003/0

Disclaimer: Consultation with a Professional Advised

The information provided here is for general informational purposes only and should not be considered as professional advice. It is essential to consult with a qualified professional or specialist before making any decisions based on the information provided. Individual circumstances and requirements vary, and a professional can provide personalized advice tailored to your specific situation. Reliance on any information provided herein is solely at your own risk.

Notes:

1: MOCP sized to not exceed 125% of the transformer primary FLA.

2: The system bonding jumper shall be sized as per CEC Rule 10-614.

3. All conductors shown are copper.