Allowable Copper conductor ampacities for cables rated not more than 5000 V and unshielded for the
installation configurations of Diagram D11
Size1/Phase
75 C Derating2/Phase
75 C Derating3/Phase75 C Derating4/Phase75 C Derating5/Phase 75 C Derating6/Phase75 C Derating8/Phase75 C Derating
1/0205182185164169150158140147130139123130115
2/0233206210186192170179159166147157139147130
3/0266236239212218193202179188167178158166147
4/0303268271240247219229203212188201178187166
250335297298264271240251222232206219194204181
300370328329291298264276245255226241214224198
350403357357316323286299265276245261231242214
400434385384340347307320284295261279247259229
500489433430381388344357316329291310275288255
600539478472418424376390346359318339300314278
750601532524464470416431382397352374331346307
900655580569504509451466413428379403357373330
1000683605593525530470485430445394419371388344
1250752666649575578512528468484429455403421373
1500804712691612614544561497513455482427445394
1750847750726643644571587520537476504447466413
2000901798744659659584601532549486515456476422

Disclaimer: Consultation with a Professional Advised

The information provided here is for general informational purposes only and should not be considered as professional advice. It is essential to consult with a qualified professional or specialist before making any decisions based on the information provided. Individual circumstances and requirements vary, and a professional can provide personalized advice tailored to your specific situation. Reliance on any information provided herein is solely at your own risk.