AWG or KCMILTable 1 (75°C)Table 2 (75°C)Table 1 (90°C)Table 2 (90°C)1/2"C (16mm)3/4"C (21mm)1"C (27mm)1.25"C (35mm)1.5"C (41mm)2"C (53mm)2.5"C (63mm)3"C (78mm)3.5"C (91mm)4" (103mm)
1430203525916254561101144200200200
123525403071220354879113175200200
1050355540591527376187134179200
870508055247131830436790116
695651057513410132332506787
412585140951247101623364963
3145100165115113681420314153
2170115190130113571117263545
119513022014511135812192533
1/02301502601701134710162228
2/0265175300195112368131823
3/0310200350225111357111519
4/03602304052601124691216
2504052554552901113571013
300445285500320111346811
35050531057035011235710
4005453356153801113579
5006203807004301112457
600690420780475111346
750785475885535111234
1000935545105561511133

Disclaimer: Consultation with a Professional Advised

The information provided here is for general informational purposes only and should not be considered as professional advice. It is essential to consult with a qualified professional or specialist before making any decisions based on the information provided. Individual circumstances and requirements vary, and a professional can provide personalized advice tailored to your specific situation. Reliance on any information provided herein is solely at your own risk.

Notes:

Conduit fill calculated based on conductor sizes per Canadian Electrical Code Part 1 – Rule 12-1014;

  1. Table 1 : Allowable Ampacities for Single Copper Conductors in free air (Based on ambient temperature of 30°C)
  2. Table 2: Allowable ampacities for not more than 3 copper conductors in raceway or cable (Based on ambient temperatures of 30°C)