AWG or KCMILTable 3 (75°C)Table 4 (75°C)Table 3 (90°C)Table 4 (90°C)1/2"C (16mm)3/4"C (21mm)1"C (27mm)1.25"C (35mm)1.5"C (41mm)2"C (53mm)2.5"C (63mm)3"C (78mm)3.5"C (91mm)4" (103mm)
855406045258141932467296124
67550855513611142435547293
410065115751248111825395368
213590150100113571218283849
115510017511511145914212837
1/01801202051351134811182431
2/0210135235150113469152026
3/0240155270175112358121722
4/0280180315205111246101418
2503152053552301113581114
3003502303952601113471012
350395250445280111246811
40042527048030511235710
5004853105453501113468
6005453406153851111356
750620385700435111345
1000950520107058511134

Disclaimer: Consultation with a Professional Advised

The information provided here is for general informational purposes only and should not be considered as professional advice. It is essential to consult with a qualified professional or specialist before making any decisions based on the information provided. Individual circumstances and requirements vary, and a professional can provide personalized advice tailored to your specific situation. Reliance on any information provided herein is solely at your own risk.

Notes:

Conduit fill calculated based on conductor sizes per Canadian Electrical Code Part 1 – Rule 12-1014;

  1. Table 3 : Allowable Ampacities for Single Aluminum Conductors in free air (Based on ambient temperature of 30°C)
  2. Table 4: Allowable ampacities for not more than 3 Aluminum conductors in raceway or cable (Based on ambient temperatures of 30°C)